IEEE 1547
Powershare Gateway meets the requirements of normal performance category B and abnormal performance category II & III of IEEE 1547-2018 IEEE Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces. The settings in the tables in this section will enable Powershare Gateway to meet the voltage and frequency ride-through requirements of IEEE 1547-2018.
CAUTION
Programming to values
outside of the ranges in this section falls outside the scope of IEEE 1547-2018.
Note
When in grid-connected mode, Powershare Gateway complies with the IEEE 1547 harmonic current distortion requirements.
| Voltage Range (% of Base Value) | Response Time |
|---|---|
| Category II | |
| 117.5<V<=120 | 0.2 s |
| 115<V<=117.5 | 0.5 s |
| 110<V<=115 | 1 s |
| Category III | |
| 110<V<=120 | 0.083 s - 12 s |
| Voltage Range (% of Base Value) | Response Time |
|---|---|
| Category II | |
| 65<=V<88 | Linear slope of 8.7 s / 1 per-unit voltage starting at 3 s @ 0.65 per-unit |
| 45<=V<65 | 0.32 s |
| 30<=V<45 | 0.16 s |
| Category III | |
| 70<=V<88 | 20 s |
| 50<=V<70 | 10 s |
| V<50 | 0.083 s - 1 s |
| Default Frequency (Hz) | Default Clearing Time (s) | Adjustable Frequency (Hz) | Adjustable Clearing Time Range (s) |
|---|---|---|---|
| >62 | 0.16 | 61.8-66 | .16-1000 |
| >61.2 | 300 | 61-66 | 180-1000 |
| <58.5 | 300 | 50-59 | 180-1000 |
| <56.6 | 0.16 | 50-57 | .16-1000 |
| Default Voltage Range (% of Base Value) | Default Clearing Time (s) | Adjustable Voltage Range (% of Base Value) | Adjustable Clearing Time Range (s) |
|---|---|---|---|
| V<45 | 0.16 | 0-50 | 0.16-2 Response faster than 1 s |
| 45<V<50 | 2 | 0-50 | 2-21 Response faster than 1 s |
| 50<V<70 | 10 | 0-88 | 2-21 |
| 70<V<88 | 21 | 0-88 | 21-50 |
| 110<V<120 | 2 | 110-120 | 1-13 |
| V>120 | 0.16 | Fixed at 120 | Fixed at 0.16 |